Product

Product

SMC-C

Home Product SMC-C

SMC-50/65/75/85C/100C Capacitor Contactor

Characteristics

SMC-C switchover capacitor contactor can switch over 3-phase single or multiple stage capacitor bank.
In conformity with IEC69047-4-1.

Product Description

Operation Parameter

Operating Times

SMC-9C,12C,18C,22C,32C,40C

240 times/h

SMC-50C,65C,75C,85C,100C

100 times/h

Electrical Endurance

SMC-9C,12C,18C,22C,32C,40C,48C

200,000 times

SMC-50C,65C,75C,85C,100C

100,000 times

● When the switch is closed, capacitor must be discharged before recharged.(Maximum residual voltage at terminals < 50V).

● To prevent short current, gG type Fuse must be 1.5~2 times than rated current.

● Switchover capacitor unit shall be connected with contactor by using impedance line.


Technical Parameter

TYPE

Rated Current(A)

Maximum Operating Power (kVar)

Applied Unit

200-240V

400-440V

550-600V

SMC-9C

14

5

9.7

14

SAC-9

SMC-12C

18

6.7

12.5

18

SAC-9

SMC-18C

24

8.5

16.7

24

SAC-9

SMC-22C

26

10

18

26

SAC-9

SMC-32C

36

15

25

36

SAC-9

SMC-40C

48

20

33.3

48

SAC-9

SMC-50C

58

22

40

58

SAC-50

SMC-65C

66

25

45.7

66

SAC-50

SMC-75C

78

29.7

54

78

SAC-50

SMC-85C

92

35

60

92

SAC-50

SMC-100C
94
37
62
94
SAC-50


Capacitor Unit Technical Parameter

Type

Contactor

Maximum Operating Power (kVar)

Rated Current

200-240V

400-440V

550-600V

SAC-9

SMC-9

5

9.7

14

14

SMC-12

6.7

12.5

18

18

SMC-18

8.5

16.7

24

24

SMC-22

10

18

26

26

SMC-32

15

25

36

36

SMC-40

20

33.3

48

48

SAC-50

SMC-50

22

40

58

58

SMC-65

25

45.7

66

66

SMC-75

29.7

54

78

78

SMC-85

35

60

92

92

SMC-100
37
62
94
94

Note:

● When the switch is closed,condenser must be discharged before recharged.(Maximum residual voltage at terminals≤50V)

● To prevent short current,gG type fuse must be 1.5~2 times than rated current.


Features of Capacitor Unit(Pre-Loading Resistor):
● Damping resister that can limit the inrush current upto 60xln is connected to the
mechanism that closed earlier than the main contact of the contactor;
● Eliminate the switching surge;
● No heat loss by the serial resistor;
● Improving the performance of the capacitor system.